Portable fire extinguishers (NFPA 10)

A monthly visual check, a yearly maintenance visit, and longer cycles for internal maintenance and hydrostatic testing.

Portable fire extinguishers: inspection and test intervals
IntervalTaskSection
Monthly (about every 30 days)Visual inspection, initialed and datedNFPA 10 §7.2 (Inspection)
Annual (not more than 1 year)Maintenance by a certified person, with a service tagNFPA 10 §7.3 (Maintenance)
Every 6 yearsInternal maintenance for stored-pressure units that need a 12-year hydrostatic testNFPA 10 §7.3 (Maintenance)
Every 5 or 12 years, by typeHydrostatic test (5 years for water, CO₂, wet chemical; 12 years for most dry chemical)NFPA 10 Ch. 8, Table 8.3.1
  • Extinguisher is in its designated place, visible, and not blocked
  • Operating instructions on the nameplate face out and are legible
  • Pressure gauge reads in the operable range
  • Safety pin and tamper seal are intact
  • No obvious physical damage, corrosion, leakage, or clogged nozzle
  • Fullness confirmed by weighing or lifting
  • Service tag or label shows the last annual maintenance date

Fire sprinkler systems (NFPA 25)

Water-based systems run on a mix of monthly, quarterly, annual and five-year tasks. The summary table is in Chapter 5.

Fire sprinkler systems: inspection and test intervals
IntervalTaskSection
Weekly or monthlyControl valve inspection: weekly if sealed, monthly if locked or electrically supervisedNFPA 25 Ch. 13 (§13.4, control valves)
MonthlyGauge inspection on wet pipe systemsNFPA 25 Ch. 5, Table 5.1.1.2
Quarterly / semiannualWaterflow alarm device test (mechanical devices quarterly; vane and pressure-switch devices semiannually)NFPA 25 §5.3.3
AnnualSprinklers, pipe, fittings and hangers inspected from the floor; main drain testNFPA 25 §5.2; §13.2.5 (main drain)
Every 5 yearsInternal pipe assessment; gauges replaced or testedNFPA 25 Ch. 14; Table 5.1.1.2
At 50 years, then every 10Sample test of standard-response sprinklersNFPA 25 §5.3.1
  • Sprinklers free of paint, corrosion, damage, loading or obstruction
  • 18 in. clearance below sprinkler deflectors kept clear of storage
  • Control valves open, sealed or supervised, and accessible
  • Gauges read normal water or air pressure
  • Waterflow alarm sounds and signals the panel
  • Main drain test result compared with earlier results
  • Spare sprinkler cabinet stocked with the right types and wrench
  • Fire department connection visible, accessible and capped

Fire alarm systems (NFPA 72)

Most devices are tested once a year. Batteries and some components carry semiannual tasks. The frequency tables are in Chapter 14.

Fire alarm systems: inspection and test intervals
IntervalTaskSection
SemiannualInspection and test of sealed lead-acid batteries and some supervisory and waterflow devicesNFPA 72 Table 14.3.1; Table 14.4.3.2
AnnualVisual inspection and functional test of initiating devices, notification appliances and the control unitNFPA 72 Table 14.3.1; Table 14.4.3.2
Per manufacturer / tableSmoke detector sensitivity testing: within 1 year of install, then every other year (longer if stable)NFPA 72 §14.4.4.3
  • Control panel shows normal, with no trouble or supervisory signals
  • Smoke and heat detectors activate and report to the panel
  • Pull stations operate and are unobstructed
  • Horns, strobes and speakers are audible and visible in the space
  • Primary and secondary (battery) power checked and load-tested
  • Signals reach the monitoring station
  • Fan shutdown, door release and elevator recall interfaces operate
  • Record of completion on file

Emergency & exit lighting (NFPA 101 (NFPA 110 for generators))

Battery units get a short monthly test and a 90-minute annual test. Generator-fed systems follow NFPA 110.

Emergency & exit lighting: inspection and test intervals
IntervalTaskSection
Monthly (30-day intervals)Functional test of at least 30 secondsNFPA 101 §7.9.3.1.1(3)
AnnualBattery units tested for the full 1½ hoursNFPA 101 §7.9.3.1.1(4)
WeeklyGenerator (EPSS) inspectionNFPA 110 §8.4.1
MonthlyGenerator exercised under load for at least 30 minutesNFPA 110 §8.4.2
  • Each unit and exit sign lights on loss of normal power
  • Exit signs are lit and readable, with arrows pointing the right way
  • Lamps and heads aimed at the egress path
  • Battery lasts the full 90 minutes on the annual test
  • Written record of each test kept for the AHJ

Self-testing/self-diagnostic units that meet NFPA 101 §7.9.3.1.2 can stand in for the manual tests; keep their reports.

Kitchen hood suppression (NFPA 17A and NFPA 96)

Wet chemical systems get a monthly owner check and a six-month service. Hood and duct cleaning depends on how hard the kitchen cooks.

Kitchen hood suppression: inspection and test intervals
IntervalTaskSection
MonthlyOwner inspection of the wet chemical systemNFPA 17A Ch. 7 (Inspection)
Every 6 monthsMaintenance and inspection by a trained, qualified personNFPA 17A Ch. 7 (Maintenance); NFPA 96 Ch. 11
AnnualFusible links replacedNFPA 17A Ch. 7
Monthly to annual, by cooking volumeExhaust system inspected for grease buildup (monthly solid fuel; quarterly high volume; semiannual moderate; annual low volume)NFPA 96 Ch. 11, Table 11.4
  • Nozzles in place, aimed at the appliances, with blow-off caps on
  • Manual pull station accessible and unobstructed
  • Gauge in range and tamper seal intact
  • Fusible links and detection line clean and current
  • Fuel or power shutoff operates on system discharge
  • Service tag shows the last six-month date
  • K-class extinguisher within 30 ft of the cooking appliances

Backflow preventers (NFPA 25 (fire lines) + state/local plumbing code and water purveyor)

On fire sprinkler lines NFPA 25 sets an annual forward flow test. The potable-water test date is set by your state or local cross-connection program and the water supplier, so it varies.

Backflow preventers: inspection and test intervals
IntervalTaskSection
AnnualForward flow test of backflow assemblies on fire protection systemsNFPA 25 §13.6
Varies, often annualPotable cross-connection test, filed with the water purveyorState/local plumbing code + water purveyor rules
  • Assembly is the approved type for the hazard (RPZ, double check, etc.)
  • Test cocks and shutoff valves operate
  • Relief valve and check valves hold at the required pressure
  • No leaks, freeze damage or bypass piping
  • Test report filed with the water purveyor on their form and deadline

Backflow testing varies by state, city and water supplier. Your water purveyor's notice is the controlling date.

Fire doors (NFPA 80)

Swinging fire door assemblies are inspected and tested at least once a year, with a written record.

Fire doors: inspection and test intervals
IntervalTaskSection
Annual (not less than)Inspection and functional test of fire door assemblies, documentedNFPA 80 §5.2
  • Labels on the door and frame are present and legible
  • No open holes or breaks in the door or frame
  • Glazing and vision lights intact and secured
  • Door, frame, hinges and hardware are aligned and working
  • No parts missing or broken
  • Clearance under the bottom no more than ¾ in.
  • Self-closing device closes the door fully from open
  • Latch engages when the door closes; no field modifications that void the label
  • No auxiliary hardware that interferes with operation; no wedges or hold-opens

National NFPA baseline, not a ruling for your building. Your state or city may adopt a different edition or add local amendments, and the authority having jurisdiction (AHJ), usually the local fire marshal, has the final word. Confirm with your local fire marshal/AHJ. Section numbers follow recent NFPA editions; your adopted edition may number them differently. Not legal advice.